Return to Home









MiniBus™
Digital Databus System

Fault modes

The MiniBus protects against these faults:

1. Short circuit or overcurrent
Each output functions as a manually-resettable electronic circuit breaker with a delayed shutdown of approximately .05 seconds (to avoid false tripping due to a surge. )

Programmable trip currents:
2.0A, 3.0A, 4.0A, 5.0A, 7.5A, 10A, 15A, 20A

2. No Load Alarm
The PDM senses the output current when the output is turned On. If there is no current, or very low current, the No Load signal is transmitted to the SIM.

The programming software allows this function to be selectable. For some applications there may be a No Load condition when the output is turned On.

3. Thermal Shutdown
The temperature of the PDM heatsink is monitored. If the temperature exceeds the design limit, the outputs will be shut down. Outputs can be programmed to shut down simultaneously, or in a priority sequence.

4. Communications Failure
If the PDM senses a communications failure, it goes into 'default output status' mode. Outputs can be programmed 'Default On' or 'Default Off'.